Backflow assembly test: Crossroads Medical Offices
ApprovedFiled Nov 23, 2025 by Morgan Calloway, Heritage Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Nov 23, 2025
- Assembly type
- DC
- Serial number
- K594835
- Size
- 4
- Test gauge serial
- G-4961
- Gauge calibration date
- Aug 3, 2025
- Check valve 1
- 4.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Morgan Calloway, current on the service date
- All required fields present
- Address matches parcel 077-57-01173
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.