Back to the backflow review queue

Backflow assembly test: 5440 Pine Knoll Rd

Approved

Filed Mar 19, 2025 by Morgan Calloway, Heritage Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Mar 19, 2025
Assembly type
DC
Serial number
K676797
Size
1
Test gauge serial
G-9168
Gauge calibration date
Apr 7, 2024
Check valve 1
0.4 psid
Check valve 1 closed tight
No
Check valve 2
2.1 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Morgan Calloway, current on the service date
  • All required fields present
  • Address matches parcel 077-49-01054
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

5440 Pine Knoll Rd
Owner: Blake Vance
Parcel 077-49-01054