Backflow assembly test: 9897 Hickory Ct

Approved

Filed Jun 8, 2026 by Alex Fairley, Heritage Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Jun 8, 2026
Assembly type
RP
Serial number
W408779
Size
3/4
Test gauge serial
G-8957
Gauge calibration date
Nov 14, 2025
Check valve 1
5 psid
Check valve 1 closed tight
Yes
Check valve 2
3.4 psid
Relief valve opened at
2.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Alex Fairley, current on the service date
  • All required fields present
  • Address matches parcel 077-46-01283
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

9897 Hickory Ct
Owner: Logan Marsh
Parcel 077-46-01283