Backflow assembly test: Blue Heron Medical Offices
ApprovedFiled Nov 7, 2026 by Jordan Wexler, Summit Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Nov 7, 2026
- Assembly type
- RP
- Serial number
- W961609
- Size
- 1
- Test gauge serial
- G-8584
- Gauge calibration date
- Mar 9, 2026
- Check valve 1
- 7.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.7 psid
- Relief valve opened at
- 3.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Jordan Wexler, current on the service date
- All required fields present
- Address matches parcel 075-64-01040
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.