Backflow assembly test: 7360 Turkey Hill Ct

Approved

Filed Oct 20, 2025 by Alex Wexler, Heritage Backflow Testing. Filed from a phone.

Report

Date of service
Oct 20, 2025
Assembly type
RP
Serial number
W736535
Size
3/4
Test gauge serial
G-7318
Gauge calibration date
Jul 7, 2025
Check valve 1
5 psid
Check valve 1 closed tight
Yes
Check valve 2
2.9 psid
Relief valve opened at
1.7 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Alex Wexler, current on the service date
  • All required fields present
  • Address matches parcel 075-27-01261
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.