Backflow assembly test: 3694 Laurel Rd
Needs reviewFiled Nov 26, 2026 by Alex Wexler, Heritage Backflow Testing. Filed from a phone.
Report
- Date of service
- Nov 26, 2026
- Assembly type
- PVB
- Serial number
- W177999
- Size
- 1
- Test gauge serial
- G-5158
- Gauge calibration date
- May 10, 2026
- Check valve 1
- 6.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Alex Wexler, current on the service date
- All required fields present
- Address matches parcel 075-30-01016
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Property
3694 Laurel Rd
Owner: Taylor Pruitt
Parcel 075-30-01016