Backflow assembly test: 4658 Pine Knoll Ln
ApprovedFiled Jul 7, 2026 by Alex Wexler, Heritage Backflow Testing. Filed from a phone.
Report
- Date of service
- Jul 7, 2026
- Assembly type
- DC
- Serial number
- Z215292
- Size
- 1
- Test gauge serial
- G-8119
- Gauge calibration date
- Jul 6, 2025
- Check valve 1
- 7.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.2 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Alex Wexler, current on the service date
- All required fields present
- Address matches parcel 075-44-01125
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
4658 Pine Knoll Ln
Owner: Jordan Fairley
Parcel 075-44-01125