Backflow assembly test: 810 Mill Creek Way
ApprovedFiled Aug 1, 2026 by Quinn Stroud, Patriot Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Aug 1, 2026
- Assembly type
- PVB
- Serial number
- Z601561
- Size
- 3/4
- Test gauge serial
- G-5121
- Gauge calibration date
- Feb 3, 2026
- Check valve 1
- 6.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Quinn Stroud, current on the service date
- All required fields present
- Address matches parcel 075-72-01036
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.