Back to the backflow review queue

Backflow assembly test: 4291 Hickory Rd

Approved

Filed Jul 22, 2025 by Jamie Vance, Patriot Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Jul 22, 2025
Assembly type
RP
Serial number
B238562
Size
3/4
Test gauge serial
G-7602
Gauge calibration date
Nov 6, 2024
Check valve 1
8.7 psid
Check valve 1 closed tight
Yes
Check valve 2
1.5 psid
Relief valve opened at
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jamie Vance, current on the service date
  • All required fields present
  • Address matches parcel 075-58-01031
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

4291 Hickory Rd
Owner: Casey Wexler
Parcel 075-58-01031