Backflow assembly test: 780 Pine Knoll Trl

Approved

Filed Jan 2, 2026 by Alex Wexler, Heritage Backflow Testing. Filed from a phone.

Report

Date of service
Jan 2, 2026
Assembly type
RP
Serial number
K332010
Size
1
Test gauge serial
G-8681
Gauge calibration date
Aug 14, 2025
Check valve 1
4.3 psid
Check valve 1 closed tight
Yes
Check valve 2
2.4 psid
Relief valve opened at
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Alex Wexler, current on the service date
  • All required fields present
  • Address matches parcel 075-97-01256
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.