Back to the backflow review queue
Backflow assembly test: 2539 Pine Knoll Ct
ApprovedFiled Mar 30, 2025 by Jordan Wexler, Summit Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Mar 30, 2025
- Assembly type
- PVB
- Serial number
- K535502
- Size
- 3/4
- Test gauge serial
- G-8130
- Gauge calibration date
- Aug 11, 2024
- Check valve 1
- 7.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Jordan Wexler, current on the service date
- All required fields present
- Address matches parcel 075-99-01023
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
2539 Pine Knoll Ct
Owner: Avery Fairley
Parcel 075-99-01023