Backflow assembly test: Riverside Grill
ApprovedFiled Sep 30, 2026 by Blake Pruitt, Patriot Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Sep 30, 2026
- Assembly type
- DC
- Serial number
- A188660
- Size
- 1 1/2
- Test gauge serial
- G-8570
- Gauge calibration date
- Feb 20, 2026
- Check valve 1
- 0.7 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 2.3 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Blake Pruitt, current on the service date
- All required fields present
- Address matches parcel 075-99-01053
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.