Backflow assembly test: 5283 Sycamore Trl

Approved

Filed Aug 8, 2026 by Alex Wexler, Heritage Backflow Testing. Filed from a phone.

Report

Date of service
Aug 8, 2026
Assembly type
RP
Serial number
W218839
Size
3/4
Test gauge serial
G-6272
Gauge calibration date
Feb 13, 2026
Check valve 1
3 psid
Check valve 1 closed tight
Yes
Check valve 2
2.7 psid
Relief valve opened at
2.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Alex Wexler, current on the service date
  • All required fields present
  • Address matches parcel 075-64-01136
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

5283 Sycamore Trl
Owner: Drew Wexler
Parcel 075-64-01136