Back to the backflow review queue

Backflow assembly test: Corner Grill

Approved

Filed Jul 23, 2026 by Rowan Kessler, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Jul 23, 2026
Assembly type
RP
Serial number
Z119043
Size
2
Test gauge serial
G-5822
Gauge calibration date
Nov 15, 2025
Check valve 1
4.1 psid
Check valve 1 closed tight
Yes
Check valve 2
1.6 psid
Relief valve opened at
3.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Rowan Kessler, current on the service date
  • All required fields present
  • Address matches parcel 073-84-01152
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

1087 Stone Gate Ct
Owner: Harlow Holdings LLC
Parcel 073-84-01152