Backflow assembly test: Blue Heron Diner

Approved

Filed Oct 26, 2025 by Rowan Kessler, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Oct 26, 2025
Assembly type
RP
Serial number
Z525602
Size
4
Test gauge serial
G-3360
Gauge calibration date
Mar 3, 2025
Check valve 1
4.5 psid
Check valve 1 closed tight
Yes
Check valve 2
3.9 psid
Relief valve opened at
1.4 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Rowan Kessler, current on the service date
  • All required fields present
  • Address matches parcel 073-84-01213
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

6184 Fox Run Dr
Owner: Marsh Holdings LLC
Parcel 073-84-01213