Backflow assembly test: Crossroads Grill
ApprovedFiled Mar 2, 2025 by Parker Okafor, Valley Backflow Testing. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Mar 2, 2025
- Assembly type
- RP
- Serial number
- K999092
- Size
- 1
- Test gauge serial
- G-7167
- Gauge calibration date
- Sep 5, 2024
- Check valve 1
- 4.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.6 psid
- Relief valve opened at
- 3.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Okafor, current on the service date
- All required fields present
- Address matches parcel 073-94-01045
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.