Back to the backflow review queue
Backflow assembly test: Crossroads Grill
ApprovedFiled Mar 7, 2024 by Logan Vance, Ridge Backflow Testing. Filed from a phone.
Report
- Date of service
- Mar 7, 2024
- Assembly type
- RP
- Serial number
- K999092
- Size
- 1
- Test gauge serial
- G-9299
- Gauge calibration date
- Oct 21, 2023
- Check valve 1
- 8.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.5 psid
- Relief valve opened at
- 2.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Logan Vance, current on the service date
- All required fields present
- Address matches parcel 073-94-01045
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
2627 Meadow Lark Way
Owner: Pruitt Holdings LLC
Parcel 073-94-01045