Backflow assembly test: Main Street Bakery

Approved

Filed Apr 2, 2024 by Parker Okafor, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Apr 2, 2024
Assembly type
RP
Serial number
W838904
Size
4
Test gauge serial
G-4383
Gauge calibration date
May 30, 2023
Check valve 1
4.4 psid
Check valve 1 closed tight
Yes
Check valve 2
1.6 psid
Relief valve opened at
1.3 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Okafor, current on the service date
  • All required fields present
  • Address matches parcel 073-74-01068
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

4159 Sycamore Way
Owner: Ellery Holdings LLC
Parcel 073-74-01068