Backflow assembly test: Maple Leaf Brewing Co

Approved

Filed Jul 11, 2026 by Logan Vance, Ridge Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Jul 11, 2026
Assembly type
RP
Serial number
B454893
Size
4
Test gauge serial
G-9911
Gauge calibration date
Oct 14, 2025
Check valve 1
7.7 psid
Check valve 1 closed tight
Yes
Check valve 2
1.2 psid
Relief valve opened at
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Logan Vance, current on the service date
  • All required fields present
  • Address matches parcel 073-11-01093
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.