Backflow assembly test: 7265 Stone Gate Ct
ApprovedFiled Dec 30, 2024 by Logan Vance, Ridge Backflow Testing. Filed from a phone.
Report
- Date of service
- Dec 30, 2024
- Assembly type
- RP
- Serial number
- Z194472
- Size
- 3/4
- Test gauge serial
- G-2006
- Gauge calibration date
- Jun 20, 2024
- Check valve 1
- 4.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.4 psid
- Relief valve opened at
- 3.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Logan Vance, current on the service date
- All required fields present
- Address matches parcel 073-93-01196
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
7265 Stone Gate Ct
Owner: Avery Hollins
Parcel 073-93-01196