Back to the backflow review queue

Backflow assembly test: Main Street Pizza

Approved

Filed Oct 10, 2026 by Rowan Kessler, Valley Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Oct 10, 2026
Assembly type
RP
Serial number
Z375278
Size
1
Test gauge serial
G-9330
Gauge calibration date
Apr 11, 2026
Check valve 1
8.3 psid
Check valve 1 closed tight
Yes
Check valve 2
3.7 psid
Relief valve opened at
2.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Rowan Kessler, current on the service date
  • All required fields present
  • Address matches parcel 073-68-01056
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

4519 Sycamore Trl
Owner: Kessler Holdings LLC
Parcel 073-68-01056