Back to the backflow review queue

Backflow assembly test: 1600 Fox Run Dr

Approved

Filed Jul 19, 2026 by Parker Okafor, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Jul 19, 2026
Assembly type
DC
Serial number
A382552
Size
1
Test gauge serial
G-8112
Gauge calibration date
Dec 1, 2025
Check valve 1
5.9 psid
Check valve 1 closed tight
Yes
Check valve 2
2.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Okafor, current on the service date
  • All required fields present
  • Address matches parcel 073-28-01071
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

1600 Fox Run Dr
Owner: Drew Hollins
Parcel 073-28-01071