Backflow assembly test: Hilltop Self Storage
ApprovedFiled Jun 30, 2025 by Parker Fairley, Heritage Backflow Testing. Filed from a phone.
Report
- Date of service
- Jun 30, 2025
- Assembly type
- RP
- Serial number
- Z906271
- Size
- 1
- Test gauge serial
- G-9658
- Gauge calibration date
- Sep 20, 2024
- Check valve 1
- 8.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.4 psid
- Relief valve opened at
- 3.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Fairley, current on the service date
- All required fields present
- Address matches parcel 073-20-01241
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.