Back to the backflow review queue
Backflow assembly test: 8076 Hickory Ct
ApprovedFiled Dec 5, 2024 by Parker Fairley, Heritage Backflow Testing. Filed from a phone.
Report
- Date of service
- Dec 5, 2024
- Assembly type
- RP
- Serial number
- A734296
- Size
- 3/4
- Test gauge serial
- G-7852
- Gauge calibration date
- Jul 31, 2024
- Check valve 1
- 7.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.9 psid
- Relief valve opened at
- 3.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Fairley, current on the service date
- All required fields present
- Address matches parcel 073-48-01311
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
8076 Hickory Ct
Owner: Morgan Fairley
Parcel 073-48-01311