Back to the backflow review queue

Backflow assembly test: 8012 Meadow Lark Ln

Approved

Filed Apr 5, 2025 by Logan Vance, Ridge Backflow Testing. Filed from a phone.

Report

Date of service
Apr 5, 2025
Assembly type
RP
Serial number
K637303
Size
1
Test gauge serial
G-6896
Gauge calibration date
Jun 15, 2024
Check valve 1
4.6 psid
Check valve 1 closed tight
Yes
Check valve 2
2.4 psid
Relief valve opened at
2.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Logan Vance, current on the service date
  • All required fields present
  • Address matches parcel 073-21-01259
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

8012 Meadow Lark Ln
Owner: Hayden Okafor
Parcel 073-21-01259