Back to the backflow review queue

Backflow assembly test: 5293 Meadow Lark Rd

Approved

Filed Sep 29, 2025 by Parker Fairley, Heritage Backflow Testing. Filed from a phone.

Report

Date of service
Sep 29, 2025
Assembly type
PVB
Serial number
K774858
Size
3/4
Test gauge serial
G-4756
Gauge calibration date
Dec 27, 2024
Check valve 1
6.2 psid
Check valve 1 closed tight
Yes
Check valve 2
1 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Fairley, current on the service date
  • All required fields present
  • Address matches parcel 073-20-01136
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

5293 Meadow Lark Rd
Owner: Parker Marsh
Parcel 073-20-01136