Backflow assembly test: 9626 Hickory Rd
Sent backFiled Nov 25, 2026 by Rowan Kessler, Valley Backflow Testing. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Nov 25, 2026
- Assembly type
- PVB
- Serial number
- Z810076
- Size
- 1
- Test gauge serial
- G-3063
- Gauge calibration date
- Jun 10, 2026
- Check valve 1
- 8.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Rowan Kessler, current on the service date
- All required fields present
- Address matches parcel 073-50-01007
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Sent back Please add the test gauge calibration certificate.
Property
9626 Hickory Rd
Owner: Morgan Marsh
Parcel 073-50-01007