Back to the backflow review queue

Backflow assembly test: Two Rivers Car Wash

Approved

Filed Jan 17, 2026 by Rowan Kessler, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Jan 17, 2026
Assembly type
RP
Serial number
K350475
Size
1 1/2
Test gauge serial
G-9188
Gauge calibration date
Jan 28, 2025
Check valve 1
3.4 psid
Check valve 1 closed tight
Yes
Check valve 2
1.1 psid
Relief valve opened at
1.8 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Rowan Kessler, current on the service date
  • All required fields present
  • Address matches parcel 073-58-01252
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

2847 Stone Gate Trl
Owner: Danner Holdings LLC
Parcel 073-58-01252