Back to the backflow review queue

Backflow assembly test: 1571 Hickory Rd

Approved

Filed May 15, 2024 by Parker Fairley, Heritage Backflow Testing. Filed from a phone.

Report

Date of service
May 15, 2024
Assembly type
DC
Serial number
W449399
Size
1
Test gauge serial
G-4154
Gauge calibration date
Dec 9, 2023
Check valve 1
6.5 psid
Check valve 1 closed tight
Yes
Check valve 2
3.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Fairley, current on the service date
  • All required fields present
  • Address matches parcel 073-59-01337
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

1571 Hickory Rd
Owner: Sam Vance
Parcel 073-59-01337