Back to the backflow review queue
Backflow assembly test: 7398 Old Church Trl
ApprovedFiled Jan 5, 2026 by Logan Vance, Ridge Backflow Testing. Filed from a phone.
Report
- Date of service
- Jan 5, 2026
- Assembly type
- RP
- Serial number
- A215740
- Size
- 3/4
- Test gauge serial
- G-8004
- Gauge calibration date
- May 6, 2025
- Check valve 1
- 3.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.5 psid
- Relief valve opened at
- 2.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Logan Vance, current on the service date
- All required fields present
- Address matches parcel 073-39-01092
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
7398 Old Church Trl
Owner: Morgan Calloway
Parcel 073-39-01092