Back to the backflow review queue

Backflow assembly test: 5084 Hickory Dr

Approved

Filed Jul 17, 2024 by Logan Vance, Ridge Backflow Testing. Filed from a phone.

Report

Date of service
Jul 17, 2024
Assembly type
RP
Serial number
Z773509
Size
3/4
Test gauge serial
G-1368
Gauge calibration date
Mar 9, 2024
Check valve 1
4.8 psid
Check valve 1 closed tight
Yes
Check valve 2
3.9 psid
Relief valve opened at
4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Logan Vance, current on the service date
  • All required fields present
  • Address matches parcel 073-23-01297
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

5084 Hickory Dr
Owner: Drew Ramirez
Parcel 073-23-01297