Back to the backflow review queue

Backflow assembly test: 5318 Sycamore Trl

Approved

Filed Apr 7, 2026 by Logan Vance, Ridge Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Apr 7, 2026
Assembly type
RP
Serial number
K431870
Size
3/4
Test gauge serial
G-9222
Gauge calibration date
Jan 7, 2026
Check valve 1
7.9 psid
Check valve 1 closed tight
Yes
Check valve 2
1.8 psid
Relief valve opened at
2.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Logan Vance, current on the service date
  • All required fields present
  • Address matches parcel 073-13-01034
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

5318 Sycamore Trl
Owner: Casey Wexler
Parcel 073-13-01034