Back to the backflow review queue

Backflow assembly test: 5318 Sycamore Trl

Approved

Filed Apr 17, 2025 by Parker Okafor, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Apr 17, 2025
Assembly type
RP
Serial number
K431870
Size
3/4
Test gauge serial
G-7999
Gauge calibration date
Sep 28, 2024
Check valve 1
3.8 psid
Check valve 1 closed tight
Yes
Check valve 2
3 psid
Relief valve opened at
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Okafor, current on the service date
  • All required fields present
  • Address matches parcel 073-13-01034
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

5318 Sycamore Trl
Owner: Casey Wexler
Parcel 073-13-01034