Back to the backflow review queue
Backflow assembly test: 7071 Old Church Ct
ApprovedFiled Oct 29, 2026 by Hayden Danner, Keystone Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Oct 29, 2026
- Assembly type
- DC
- Serial number
- K649578
- Size
- 3/4
- Test gauge serial
- G-5607
- Gauge calibration date
- Aug 7, 2026
- Check valve 1
- 4.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Hayden Danner, current on the service date
- All required fields present
- Address matches parcel 071-48-01117
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
7071 Old Church Ct
Owner: Drew Calloway
Parcel 071-48-01117