Backflow assembly test: 8918 Mill Creek Rd

Approved

Filed Jul 4, 2025 by Blake Danner, Summit Backflow Testing. Filed from a phone.

Report

Date of service
Jul 4, 2025
Assembly type
RP
Serial number
B395485
Size
1
Test gauge serial
G-5884
Gauge calibration date
Feb 7, 2025
Check valve 1
4.1 psid
Check valve 1 closed tight
Yes
Check valve 2
2.9 psid
Relief valve opened at
2.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Blake Danner, current on the service date
  • All required fields present
  • Address matches parcel 071-50-01308
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

8918 Mill Creek Rd
Owner: Parker Ramirez
Parcel 071-50-01308