Back to the backflow review queue

Backflow assembly test: 9625 Ridgeview Ct

Approved

Filed Jun 4, 2025 by Blake Danner, Summit Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Jun 4, 2025
Assembly type
RP
Serial number
A530061
Size
1
Test gauge serial
G-9948
Gauge calibration date
Mar 2, 2025
Check valve 1
3.3 psid
Check valve 1 closed tight
Yes
Check valve 2
2.6 psid
Relief valve opened at
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Blake Danner, current on the service date
  • All required fields present
  • Address matches parcel 071-40-01333
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

9625 Ridgeview Ct
Owner: Jordan Wexler
Parcel 071-40-01333