Back to the backflow review queue

Backflow assembly test: Blue Heron Apartments

Approved

Filed Sep 2, 2026 by Blake Danner, Summit Backflow Testing. Filed from a phone.

Report

Date of service
Sep 2, 2026
Assembly type
DC
Serial number
Z957074
Size
4
Test gauge serial
G-3369
Gauge calibration date
Aug 24, 2025
Check valve 1
0.9 psid
Check valve 1 closed tight
No
Check valve 2
3.2 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Blake Danner, current on the service date
  • All required fields present
  • Address matches parcel 071-13-01033
  • Test gauge calibration is more than a year old.
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

3255 Fox Run Dr
Owner: Ellery Holdings LLC
Parcel 071-13-01033