Backflow assembly test: 3389 Fox Run Ln
ApprovedFiled Dec 26, 2023 by Quinn Okafor, Heritage Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Dec 26, 2023
- Assembly type
- RP
- Serial number
- B726090
- Size
- 3/4
- Test gauge serial
- G-3574
- Gauge calibration date
- Nov 18, 2022
- Check valve 1
- 0.9 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3 psid
- Relief valve opened at
- 3.9 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Quinn Okafor, current on the service date
- All required fields present
- Address matches parcel 071-51-01004
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
3389 Fox Run Ln
Owner: Avery Benton
Parcel 071-51-01004