Back to the backflow review queue

Backflow assembly test: 9585 Quarry Dr

Approved

Filed Dec 24, 2025 by Jordan Vance, Heritage Plumbing & Backflow. Filed from a phone.

Report

Date of service
Dec 24, 2025
Assembly type
RP
Serial number
A463214
Size
1
Test gauge serial
G-3437
Gauge calibration date
May 24, 2025
Check valve 1
8.2 psid
Check valve 1 closed tight
Yes
Check valve 2
1.9 psid
Relief valve opened at
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jordan Vance, current on the service date
  • All required fields present
  • Address matches parcel 071-66-01301
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.