Back to the backflow review queue

Backflow assembly test: 6610 Stone Gate Ln

Approved

Filed Oct 8, 2026 by Avery Whitcomb, Keystone Plumbing & Backflow. Filed from a phone.

Report

Date of service
Oct 8, 2026
Assembly type
DC
Serial number
Z398779
Size
3/4
Test gauge serial
G-5111
Gauge calibration date
Aug 10, 2026
Check valve 1
4.2 psid
Check valve 1 closed tight
Yes
Check valve 2
2.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Whitcomb, current on the service date
  • All required fields present
  • Address matches parcel 071-18-01026
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

6610 Stone Gate Ln
Owner: Jordan Hollins
Parcel 071-18-01026