Backflow assembly test: 4417 Hickory Dr

Approved

Filed Sep 27, 2024 by Drew Hollins, Summit Backflow Testing. Filed from a phone.

Report

Date of service
Sep 27, 2024
Assembly type
RP
Serial number
Z435394
Size
1
Test gauge serial
G-5925
Gauge calibration date
Jan 20, 2024
Check valve 1
7.7 psid
Check valve 1 closed tight
Yes
Check valve 2
3.2 psid
Relief valve opened at
3.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Drew Hollins, current on the service date
  • All required fields present
  • Address matches parcel 071-96-01203
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

4417 Hickory Dr
Owner: Alex Pruitt
Parcel 071-96-01203