Back to the backflow review queue

Backflow assembly test: 6509 Quarry Dr

Approved

Filed Oct 28, 2024 by Drew Hollins, Summit Backflow Testing. Filed from a phone.

Report

Date of service
Oct 28, 2024
Assembly type
RP
Serial number
K867448
Size
1
Test gauge serial
G-2822
Gauge calibration date
Aug 28, 2024
Check valve 1
7.5 psid
Check valve 1 closed tight
Yes
Check valve 2
1.5 psid
Relief valve opened at
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Drew Hollins, current on the service date
  • All required fields present
  • Address matches parcel 071-71-01037
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

6509 Quarry Dr
Owner: Shawn Danner
Parcel 071-71-01037