Back to the backflow review queue

Backflow assembly test: 2816 Ridgeview Ct

Approved

Filed Apr 5, 2025 by Blake Danner, Summit Backflow Testing. Filed from a phone.

Report

Date of service
Apr 5, 2025
Assembly type
RP
Serial number
B964886
Size
1
Test gauge serial
G-6642
Gauge calibration date
Nov 22, 2024
Check valve 1
7.7 psid
Check valve 1 closed tight
Yes
Check valve 2
1.8 psid
Relief valve opened at
2.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Blake Danner, current on the service date
  • All required fields present
  • Address matches parcel 071-10-01273
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

2816 Ridgeview Ct
Owner: Avery Brandt
Parcel 071-10-01273