Back to the backflow review queue

Backflow assembly test: 9051 Sycamore Trl

Approved

Filed Jun 19, 2025 by Jordan Vance, Heritage Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Jun 19, 2025
Assembly type
RP
Serial number
B752524
Size
1
Test gauge serial
G-9745
Gauge calibration date
Sep 26, 2024
Check valve 1
8.3 psid
Check valve 1 closed tight
Yes
Check valve 2
2.2 psid
Relief valve opened at
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jordan Vance, current on the service date
  • All required fields present
  • Address matches parcel 071-89-01242
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

9051 Sycamore Trl
Owner: Reese Whitcomb
Parcel 071-89-01242