Back to the backflow review queue
Backflow assembly test: 5114 Fox Run Ln
ApprovedFiled Aug 25, 2025 by Avery Whitcomb, Keystone Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Aug 25, 2025
- Assembly type
- RP
- Serial number
- A529005
- Size
- 1
- Test gauge serial
- G-8757
- Gauge calibration date
- Dec 16, 2024
- Check valve 1
- 8.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.6 psid
- Relief valve opened at
- 2.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Avery Whitcomb, current on the service date
- All required fields present
- Address matches parcel 071-41-01235
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
5114 Fox Run Ln
Owner: Cameron Okafor
Parcel 071-41-01235