Back to the backflow review queue

Backflow assembly test: 4217 Spring Branch Trl

Approved

Filed Dec 27, 2025 by Sam Nguyen, Keystone Plumbing & Backflow. Filed from a phone.

Report

Date of service
Dec 27, 2025
Assembly type
RP
Serial number
A710193
Size
1
Test gauge serial
G-4145
Gauge calibration date
Sep 4, 2025
Check valve 1
8.9 psid
Check valve 1 closed tight
Yes
Check valve 2
1.3 psid
Relief valve opened at
4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Sam Nguyen, current on the service date
  • All required fields present
  • Address matches parcel 071-60-01240
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

4217 Spring Branch Trl
Owner: Drew Stroud
Parcel 071-60-01240