Backflow assembly test: 4217 Spring Branch Trl

Approved

Filed Dec 22, 2024 by Quinn Okafor, Heritage Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Dec 22, 2024
Assembly type
RP
Serial number
A710193
Size
1
Test gauge serial
G-4940
Gauge calibration date
May 18, 2024
Check valve 1
3.7 psid
Check valve 1 closed tight
Yes
Check valve 2
3.7 psid
Relief valve opened at
3.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Quinn Okafor, current on the service date
  • All required fields present
  • Address matches parcel 071-60-01240
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.