Back to the backflow review queue
Backflow assembly test: 2665 Laurel Ct
ApprovedFiled Mar 7, 2025 by Drew Hollins, Summit Backflow Testing. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Mar 7, 2025
- Assembly type
- RP
- Serial number
- A409276
- Size
- 3/4
- Test gauge serial
- G-6925
- Gauge calibration date
- Dec 10, 2023
- Check valve 1
- 5.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.1 psid
- Relief valve opened at
- 1.6 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Drew Hollins, current on the service date
- All required fields present
- Address matches parcel 071-45-01112
- RP relief valve must open at 2.0 psid or more.
- Test gauge calibration is more than a year old.
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.