Backflow assembly test: 2665 Laurel Ct
ApprovedFiled Feb 19, 2024 by Hayden Danner, Keystone Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Feb 19, 2024
- Assembly type
- RP
- Serial number
- A409276
- Size
- 3/4
- Test gauge serial
- G-4812
- Gauge calibration date
- Jan 6, 2024
- Check valve 1
- 7.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.7 psid
- Relief valve opened at
- 2.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Hayden Danner, current on the service date
- All required fields present
- Address matches parcel 071-45-01112
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.