Backflow assembly test: 4739 Mill Creek Ct

Approved

Filed Jun 30, 2025 by Avery Benton, Keystone Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Jun 30, 2025
Assembly type
PVB
Serial number
A313902
Size
1
Test gauge serial
G-7026
Gauge calibration date
Mar 5, 2025
Check valve 1
4.6 psid
Check valve 1 closed tight
Yes
Check valve 2
1.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Benton, current on the service date
  • All required fields present
  • Address matches parcel 067-15-01121
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.